| Sign In | Join Free | My benadorassociates.com | 
              
  | 
      
Brand Name : P+F
Model Number : KFA6-SR2-Ex2.W
Certification : PTB 00 ATEX 2081
Place of Origin : Germany
MOQ : 1 piece
Price : negotiable
Payment Terms : T/T
Supply Ability : 100pcs per month
Delivery Time : on request
Packaging Details : standard carton packing
Signal type : Digital Input
Supply Connection : terminals 14, 15
Safety Integrity Level (SIL) : SIL 2
Degree of protection : IEC 60529:2001
Display elements : LEDs
Electromagnetic compatibility : NE 21:2006
Ambient temperature : -20 ... 60 °C (-4 ... 140 °F)
Dimensions : 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
2-channel isolated barrier, 230 V AC supply, Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 207 ... 253 V AC, 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (change-over contact), Reversible mode of operation
Technical Data
|  			 General specifications  |  		||
|---|---|---|
|  			 Signal type  |  			 			 Digital Input  |  		|
|  			 Functional safety related parameters  |  		||
|  			 Safety Integrity Level (SIL)  |  			 			 SIL 2  |  		|
|  			 Supply  |  		||
|  			 Connection  |  			 			 terminals 14, 15  |  		|
|  			 Rated voltage  |  			 			 207 ... 253 V AC, 45 ... 65 Hz  |  		|
|  			 Power dissipation  |  			 			 1.2 W  |  		|
|  			 Power consumption  |  			 			 max. 1.3 W  |  		|
|  			 Input  |  		||
|  			 Connection side  |  			 			 field side  |  		|
|  			 Connection  |  			 			 terminals 1+, 2+, 3-; 4+, 5+, 6-  |  		|
|  			 Rated values  |  			 			 acc. to EN 60947-5-6 (NAMUR)  |  		|
|  			 Open circuit voltage/short-circuit current  |  			 			 approx. 8 V DC / approx. 8 mA  |  		|
|  			 Switching point/switching hysteresis  |  			 			 1.2 ... 2.1 mA / approx. 0.2 mA  |  		|
|  			 Line fault detection  |  			 			 breakage I ≤ 0.1 mA , short-circuit I > 6 mA  |  		|
|  			 Pulse/Pause ratio  |  			 			 min. 20 ms / min. 20 ms  |  		|
|  			 Output  |  		||
|  			 Connection side  |  			 			 control side  |  		|
|  			 Connection  |  			 			 output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12  |  		|
|  			 Output I, II  |  			 			 signal ; relay  |  		|
|  			 Contact loading  |  			 			 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load  |  		|
|  			 Energized/De-energized delay  |  			 			 approx. 20 ms / approx. 20 ms  |  		|
|  			 Mechanical life  |  			 			 107 switching cycles  |  		|
|  			 Transfer characteristics  |  		||
|  			 Switching frequency  |  			 			 ≤ 10 Hz  |  		|
|  			 Galvanic isolation  |  		||
|  			 Input/Output  |  			 			 reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff  |  		|
|  			 Input/power supply  |  			 			 reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff  |  		|
|  			 Output/power supply  |  			 			 reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff  |  		|
|  			 Output/Output  |  			 			 reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff  |  		|
|  			 Indicators/settings  |  		||
|  			 Display elements  |  			 			 LEDs  |  		|
|  			 Labeling  |  			 			 space for labeling at the front  |  		|
|  			 Directive conformity  |  		||
|  			 Electromagnetic compatibility  |  			 			 
  |  		|
|  			 
  |  			 			 Directive 2014/30/EU  |  			 			 EN 61326-1:2013 (industrial locations)  |  		
|  			 Low voltage  |  			 			 
  |  		|
|  			 
  |  			 			 Directive 2014/35/EU  |  			 			 EN 61010-1:2010  |  		
|  			 Conformity  |  		||
|  			 Electromagnetic compatibility  |  			 			 NE 21:2006  |  		|
|  			 Degree of protection  |  			 			 IEC 60529:2001  |  		|
|  			 Input  |  			 			 EN 60947-5-6:2000  |  		|
|  			 Ambient conditions  |  		||
|  			 Ambient temperature  |  			 			 -20 ... 60 °C (-4 ... 140 °F)  |  		|
|  			 Mechanical specifications  |  		||
|  			 Degree of protection  |  			 			 IP20  |  		|
|  			 Connection  |  			 			 screw terminals  |  		|
|  			 Mass  |  			 			 approx. 150 g  |  		|
|  			 Dimensions  |  			 			 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2  |  		|
|  			 
  |  			 			 Height  |  			 			 119 mm  |  		
|  			 
  |  			 			 Width  |  			 			 20 mm  |  		
|  			 
  |  			 			 Depth  |  			 			 115 mm  |  		
|  			 Mounting  |  			 			 on 35 mm DIN mounting rail acc. to EN 60715:2001  |  		|
|  			 Data for application in connection with hazardous areas  |  		||
|  			 EU-type examination certificate  |  			 			 PTB 00 ATEX 2081  |  		|
|  			 
  |  			 			 Marking  |  			 			 
  |  		
|  			 
  |  			 			 Input  |  			 			 Ex ia  |  		
|  			 
  |  			 			 Voltage  |  			 			 10.6 V  |  		
|  			 
  |  			 			 Current  |  			 			 19.1 mA  |  		
|  			 
  |  			 			 Power  |  			 			 51 mW (linear characteristic)  |  		
|  			 Supply  |  			 			 
  |  		|
|  			 
  |  			 			 Maximum safe voltage  |  			 			 253 V AC (Attention! Um is no rated voltage.)  |  		
|  			 Output  |  			 			 
  |  		|
|  			 
  |  			 			 Contact loading  |  			 			 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load  |  		
|  			 
  |  			 			 Maximum safe voltage  |  			 			 253 V AC (Attention! The rated voltage can be lower.)  |  		
|  			 Galvanic isolation  |  			 			 
  |  		|
|  			 
  |  			 			 Input/input  |  			 			 not available  |  		
|  			 
  |  			 			 Input/Output  |  			 			 safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V  |  		
|  			 
  |  			 			 Input/power supply  |  			 			 safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V  |  		
|  			 Directive conformity  |  			 			 
  |  		|
|  			 
  |  			 			 Directive 2014/34/EU  |  			 			 EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012  |  		
|  			 International approvals  |  		||
|  			 FM approval  |  			 			 
  |  		|
|  			 
  |  			 			 Control drawing  |  			 			 116-0035  |  		
|  			 UL approval  |  			 			 
  |  		|
|  			 
  |  			 			 Control drawing  |  			 			 116-0145  |  		
|  			 CSA approval  |  			 			 
  |  		|
|  			 
  |  			 			 Control drawing  |  			 			 116-0047  |  		
|  			 IECEx approval  |  			 			 
  |  		|
|  			 
  |  			 			 IECEx certificate  |  			 			 IECEx PTB 11.0031  |  		
|  			 
  |  			 			 IECEx marking  |  			 			 [Ex ia Ga] IIC  |  		
Related Models:
|  			 KFU8-UFT  |  			 			 KFD0-CS-Ex1.51P  |  		
|  			 K-HM26-2M-261533  |  			 			 KFD0-CS-Ex2.50P  |  		
|  			 NBB15-U1-E2  |  			 			 KFD0-CS-Ex2.51P  |  		
|  			 NBB1,5-5GM25-E2  |  			 			 KFD0-RO-Ex2  |  		
|  			 NBB1,5-5GM25-E2-V3  |  			 			 KFD0-SCS-Ex1.55  |  		
|  			 NBB1,5-F79-E0  |  			 			 KFD0-SD2-Ex2.1045  |  		
|  			 NBB1,5-F79-E2  |  			 			 KFD0-SD2-Ex2.1245  |  		
|  			 NBB15-U1-Z2  |  			 			 KFD0-TR-Ex1  |  		
|  			 NBB5-18GM50-E2-V1  |  			 			 KFD0-CC-1  |  		
|  			 NBB15-30GM30-E2-V1  |  			 			 KFD0-HMS-16  |  		
|  			 NBB15-30GM50-A2-V1  |  			 			 KFD0-RSH-1.4S.PS2  |  		
|  			 NBB15-30GM50-E2  |  			 			 KFD0-SD2-EX1.10100  |  		
|  			 NBB15-30GM50-E2-M  |  			 			 KFD0-SD2-EX1.1045  |  		
|  			 NBB15-30GM50-E2-V1  |  			 			 KFD2-UT2-1  |  		
|  			 NBB15-30GM50-E2-V1-M  |  			 			 KFD2-CD-1.32  |  		
|  			 NBB8-18GM30-E2  |  			 			 KFD2-CD-EX1.32  |  		
|  			 NBB8-18GM30-E2-V1  |  			 			 KFD2-HMM-16  |  		
|  			 NBB8-18GM60-A2-V1  |  			 			 KFD2-SH-EX1.T  |  		
|  			 NJ4-12GK-SN  |  			 			 KFD2-UT2-1  |  		
|  			 NJ5-18GK-N  |  			 			 KFD2-VR4-EX1.26  |  		
|  			 NJ5-18GK-N-150  |  			 			 KFU8-UFC-1.D  |  		
|  			 NJ5-18GM-N  |  			 			 V15-G-2M  |  		
|  			 NJ8-18GK-N  |  			 			 Z 787  |  		
|  			 RD0-FB-EX4  |  			 			 Z787.H  |  		
|  			 RD0-TI-Ex8.FF.*  |  			 			 HIC2031  |  		
|  			 Z787.F  |  			 			 Z787.H.F  |  		



| 
                                             | 
                
                        KFA6-SR2-Ex2.W Switch Amplifier SIL 2 P+F Sensors Digital Input Images |